Harold, opto couplers are a good idea up to 10KV isolation. Isolated supply at 10KV it's usually expensive but up to 1KV it's easy to find: http://www.newark.com/recom-power/roe-0505s/dc-dc-converter-1w-5v-0-2a-sip/= dp/63X9545 Buried cable is less susceptible to lighting. I will not be extremely worried but depends what do you have at the end. Vasile On Sat, May 16, 2015 at 8:39 PM, Harold Hallikainen wrote: > I'm working on an application where contact closures will be sensed by a > PIC inside a building, but the contacts are outside (perhaps tens of > meters away). What sort of protection for the inputs is suggested? What > sort of protection is required by regulatory standards for equipment > connecting to outside wiring? The outside wiring would likely be buried, > but lightning could still induce currents into buried cables. Opto > couplers are one way to get the isolation, but then you have to power the > LEDs with an isolated supply. Ideas? > > Thanks! > > Harold > > > > -- > FCC Rules Updated Daily at http://www.hallikainen.com - Advertising > opportunities available! > Not sent from an iPhone. > -- > http://www.piclist.com/techref/piclist PIC/SX FAQ & list archive > View/change your membership options at > http://mailman.mit.edu/mailman/listinfo/piclist > --=20 http://www.piclist.com/techref/piclist PIC/SX FAQ & list archive View/change your membership options at http://mailman.mit.edu/mailman/listinfo/piclist .