On 8/28/2013 9:03 PM, Carl Denk wrote: > I have several digital controlled relays @ 12 VDC coils, the coils are > powered from a PLC. If 2 or so relaycoils are connected in parallel, > should I have one diode across the coil terminals of every relay? If > only one relay requires a diode, should it be at the nearest or farthest > coil from the driver. The relays are located within inches of each other > and more than 20' of cable to the driver IC. More than one relay is > required since I am using 4PDT relays and I have more than 4 circuits to > switch. > > Thanks ahead for replies :) Closest to the relay, possibly between the pins if the relay layout=20 allows it. I typically use 1n4004 diodes because they are a common part=20 and cheap. One per relay is what I would do. Mark --=20 http://www.piclist.com/techref/piclist PIC/SX FAQ & list archive View/change your membership options at http://mailman.mit.edu/mailman/listinfo/piclist .