On Sat, 06 Jul 2013 16:42:58 -0400, you wrote: >I will be building a small network of 4 clients to send one of the=20 >house's 4 heating/cooling zones temperature and humidity to a central=20 >processor. The client likely will be 18F1320, and the processor 18F4320=20 >since I have a few laying around, but could consider something=20 >different. The client will also have a LCD display. The processor will=20 >based on temperature and humidity sent the house HVAC zone controller=20 >and humidifier signals (24VAC) via relays based on current set conditions. > >The 4 zone lengths from the processor range from 10 to 50 feet and=20 >planning to use cat-5 cable. 2 pair for power to the client, and one=20 >pair for RS-485 signal. The network speed can be very slow, even down to=20 >300 baud, since 1 message from each client in 1second and a message=20 >length of maybe 20 characters at most would be a lot. > >The question is: Will a star arrangement work, and what should the=20 >terminating resistors be? That will work fine up to a good few kbaud, no need for terminators at that= distance --=20 http://www.piclist.com/techref/piclist PIC/SX FAQ & list archive View/change your membership options at http://mailman.mit.edu/mailman/listinfo/piclist .