According to EN 61010, which may not be exactly as UL 61010, a hipot test = (dielectric strength) at 840VAC corresponds to 0.5mm clearance through basi= c = insulation. BUT the correspondeing DC value should then be 1200VDC accordin= g to = table 9 and not 1080VDC so the values may come elswere from. The clearance depends on a lot of factors - type of insulation, pullotion = degree, category of measuring circuit, transient voltages, rated operating = altitude, working voltage, combination of voltages for different circuits, = mains voltage where the circuit is used and possibly more. So a hipot test may not be irrelevant. You should be able to get the paragraphs in 61010 where these requirements = and = values are stated (it should be in the test report). /Ruben > Mike Hord wrote: > = > >>So, did ETL make a mistake in specifying a hipot test? Or am I missing > >>something in the UL-61010 requirements? > >> > >>You should DEFINITELY ask them both whether the test is truly > >>needed AND what the point of the test is. If the person you ask > >>doesn't know, push the matter- someone has to, or you're just being > >>asked to destroy one of your (expensive?) devices for no good reason. > >> > >>Mike H. > >> = > >> > Thanks for the response Mike. > I have. And the exact response I've received so far--because we said = > so. And yes, it definitely will kill low voltage devices. And it's not = > just supposed to be a sample, it's 100% of production. This is the same = > project I asked the testing engineer how to calculate DC power -- and he = > didn't have a clue! That's why I'm getting very suspicious of this = > organization and I've had more than a few hackles raised over this projec= t. > = > Bill > -- = > http://www.piclist.com PIC/SX FAQ & list archive > View/change your membership options at > http://mailman.mit.edu/mailman/listinfo/piclist > = =3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D= =3D=3D=3D=3D=3D Ruben J=F6nsson AB Liros Electronic Box 9124, 200 39 Malm=F6, Sweden TEL INT +46 40142078 FAX INT +46 40947388 ruben@pp.sbbs.se =3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D= =3D=3D=3D=3D=3D -- = http://www.piclist.com PIC/SX FAQ & list archive View/change your membership options at http://mailman.mit.edu/mailman/listinfo/piclist