IEC555-5 I think it is referenced by several specs for various telecoms gear (2Kv ac for 1m followed by megger at 500vdc should be greater than 100M or 20M if a number of circuits are tested. This standard is applied to all DC gear attached to the rail network and the spec is indexed by EN50121-4 and -5 this is the standard applied to all battery charging systems that we make. Rgds Steve -----Original Message----- From: piclist-bounces@mit.edu [mailto:piclist-bounces@mit.edu] On Behalf Of alan smith Sent: 10 January 2006 15:33 To: Microcontroller discussion list - Public. Subject: [EE] hipot tests for 48VDC bus Does anyone happen to have the specs on what voltage you test for when doing a DC hipot test on a 48VDC distribution system? We could just ask our bus bar vendor to provide a document saying it passes, but would like to know what the standard specs are to test against. thanks in advance -Al --------------------------------- Yahoo! Photos - Showcase holiday pictures in hardcover Photo Books. You design it and we'll bind it! -- http://www.piclist.com PIC/SX FAQ & list archive View/change your membership options at http://mailman.mit.edu/mailman/listinfo/piclist -- http://www.piclist.com PIC/SX FAQ & list archive View/change your membership options at http://mailman.mit.edu/mailman/listinfo/piclist