> Stealing your thread for a somewhat related question. I want to > use a 220V 30A dryer outlet (no longer used since we have a gas > dryer) for a subpanel in an _attached_ garage. I want 2x 120V 20A > circuts for a table saw, air compressor, etc. After turning off > the breaker I removed the outlet and found H-H-N (no ground). > Sounds like I might be outta luck. > You could repurpose your existing conductors as H-N-G. Feed with one side of the existing 30A breaker. Put in a subpanel with two 20A breakers. You will have two 20A circuits, but you can't you them both to full capacity at the same time. Bob Ammerman RAm Systems -- http://www.piclist.com hint: The list server can filter out subtopics (like ads or off topics) for you. See http://www.piclist.com/#topics