Al, On Wed, 10 Mar 2004 07:11:19 -0800, al smith wrote: > I did some measurements, where I found peak current for 122VAC single phase > to be 1.554A being pulled on the AC, and then did the same test using 212VAC > (two legs of a 208 3 phase) and found the AC current draw to be 0.935A This has always perplexed me: surely if you're connecting across 2 of 3 phases (something we don't do in the UK) then the voltages are at 120 degrees phase angle to each other, so you will be getting a distorted waveform, not a sine wave? > Thus wattage is 189.6 for single phase, and 198W for the '3phase'. Pretty > close in value, although I might expect them to be pretty much the same, > since the same load was applied. So thats the first curious item. Unless you're using "True RMS" meters, I think the distortion I mention would mean that the readings would be skewed. > Then, using the formula A=W/(V*pf*1.73) I get a pf of 0.58, much lower > than I might expect. So is there a relationship of the pf related to > voltage? I would tend to think not, as its the comparison of apparent vs > real power, or the efficency of the supply. I wonder if running it using > two of the 3 legs of a 3 phase power has anything to do with it? I do have > a variac, so maybe I will run the same test, using a single phase 212VAC and > see if there are any differences. I'd be interested to hear the results - and to see a 'scope trace of the waveform, so I can see if I was right! :-) Incidentally, is power factor correction (PFC) a Good Thing for the user (ie. does the meter go round less for a given power used) or for the supplier (the meter goes round more)? Cheers, Howard Winter St.Albans, England -- http://www.piclist.com#nomail Going offline? Don't AutoReply us! email listserv@mitvma.mit.edu with SET PICList DIGEST in the body