> > >The 12.6V transformer output is rated with the primary at > 230V. Now I am > > >considering using it on 277VAC. This should bring the > input to the 7805 > up > > >to about 120% of the 8.9V, 0r about 10.7V. > > > > Don't do that! > > > > I think that you will cook your transformer if you > over-voltage the input > > that much. Core saturation. > > Doesn't core saturation depend on current, rather than > voltage? I would > think that you'd have less chance of saturating at 277V than 230V. > > Bob Ammerman > RAm Systems > But no-load current depends heavily on primary coil voltage. How about having 1A no-load current with 277V? (Core saturation). Mike. -- http://www.piclist.com hint: To leave the PICList mailto:piclist-unsubscribe-request@mitvma.mit.edu