I don't know how big the generator is but the "ship" in this case is actually a FPSO, like an oil tanker perminately moored to a group of oil wells for crude oil processing and storage. So I think the generator will be pretty big. Our current trailer is set up for 220V single phase. 2.5kW + 4 people + 3 computers + 1 coffee pot kept it warm during a Maine winter. I should probably ask the FPSO people if a 2.5kW imbalance is a problem. I was hoping there was some mystical way to keep the load balanced. 3 phase is new to me. Sherpa Doug > -----Original Message----- > From: Peter L. Peres [mailto:plp@ACTCOM.CO.IL] > Sent: Tuesday, July 31, 2001 12:33 PM > To: PICLIST@MITVMA.MIT.EDU > Subject: [EE]: 3 Phase Power distribution > > > 2.5kW is too much inbalance for a 50kW generator (5%). Others may not > aggree. > > I'd suggest 3 x 1kW heaters each on its phase. 2.5 kW is not > nearly enough > for people in a deck mounted container, unless it's specially > insulated. > > But I am not an expert. > > Peter > > -- > http://www.piclist.com hint: PICList Posts must start with ONE topic: > [PIC]:,[SX]:,[AVR]: ->uP ONLY! [EE]:,[OT]: ->Other [BUY]:,[AD]: ->Ads > > > -- http://www.piclist.com hint: PICList Posts must start with ONE topic: [PIC]:,[SX]:,[AVR]: ->uP ONLY! [EE]:,[OT]: ->Other [BUY]:,[AD]: ->Ads