IIRC, The National Electric Code specifically prohibits using a common neutral between the two phases. With the neutral's only tied together at the service panel you avoid a very dangerous situation when a neutral goes open outside the service panel. ___ 120VAC | |-----------x <----------x | S | | | | V | [100W bulb] | | C | N | | | E |-----------x 240VAC | | | | P |-----------x | | A | N | | | N | [500W load] | | E | | | | L |-----------x <----------x --- 120VAC Paul ========================================= Paul Hutchinson Chief Engineer Maximum Inc., 30 Samuel Barnet Blvd. New Bedford, MA 02745 phutchinson@imtra.com http://www.maximum-inc.com ========================================= -- http://www.piclist.com hint: PICList Posts must start with ONE topic: [PIC]:,[SX]:,[AVR]: ->uP ONLY! [EE]:,[OT]: ->Other [BUY]:,[AD]: ->Ads