Dwayne Reid wrote: >David Duffy wrote: > >>Sounds simple(ish) & obvious! Hmmm, why didn't I think of it? :-) >>I may be able to get away with a power resistor in series with the >>supply line (between battery & drivers) to limit the current. A lamp >>would work even better but can't afford an O/C filament to stop the >>unit from working. The battery supply is 24Vdc and the unit will be >>for firing fireworks "electric matches" or igniters by remote control. > >The fireworks / pyro control systems that my company manufactures does >things a little differently: the channel 'arm' relay connects one side of >the igniter to the high side of the battery. A current sense FET (IRCZ24) >is turned on when the channel is to be fired. The current limit is set to >about 6 amps or so. > >Both sides of the ignitor are shunted by the normally closed contacts of >the arm relay while the channel is not armed. In addition, both sides of >the ignitor are floated above ground by a few volts and monitored to look >for ground shorts or leakage. Its kind of a bridge circuit - if something >upsets the balance, that channel is locked out and a fault indication is >sent back to master control. > >Each firing channel uses 3 sections of LM2901 quad comparitor (2 sections >for the bridge and 1 section for continuity detector), 1 section of LM2904 >dual op-amp (FET driver / current limit), 1 section of NEC EPE series dual >relay (great little dual 30 Amp SPDT relay), 1 IRCZ24 FET, and about 1/4 of >a EPM7032SLC-44 epld from altera. The epld does all the timing and serial >communications as well as the fault / arm / fire logic required. > >In a nutshell, that is how I did our system. > >Look over your requirements carefully - there may be no need to use a high >side driver. It is dead simple to build a current limited low side driver >using a sense FET and a single section of op-amp. As a bonus, the op-amp >takes care of level translation from your logic supply to the drive >required for the FET. The caveat is that you must control what happens >with the high side supply. My system monitors for faults before it allows >the ignitor to be connected to the high side, but this requires an arm >relay for each channel. This is a tradeoff that I was happy to accept. The reason I was going for a high side driver was that this unit is to replace a manual switch firing unit that uses a common ground system on the firing rails (right name for them?). Each rail has 20 outputs on it with a D25 connector. I suppose I could use the existing rails but the +/- markings on each channel would be back to front . (Actually red/black spring terminals) Getting 100 channels in a small space is going to be difficult & expensive. Regards... -- http://www.piclist.com hint: The list server can filter out subtopics (like ads or off topics) for you. See http://www.piclist.com/#topics